Technical Documentation "Installation, Mounting and Operating Instructions" BAK-250 Fire protection unit General building supervisory approval Z-41.3-542 SCHAKO | Ferdinand Schad KG Steigstraße 25-27 D-78600 Kolbingen
Abrir la página 1 del catálogovchAko Fire protection unit BAK-250 Technical documentation Description VENTILATION FITTINGS Exhaust air: DQJA-SR-A DQJA-SQ-A 4-DE-A DQD-L 4-DF Weight of the fire protection unit Exposed ceiling constructions can loose their strength pre-maturely. To avoid this ceiling constructions are protected with fire resistant suspended ceilings. Openings in the suspended ceiling, for example for air diffusers, are only permit-ted if they can be closed in case of fire with suitable fire protection equipment, for example with the fire protection unit type BAK-250. Fire protection unit type BAK-250 with...
Abrir la página 2 del catálogoíli^ Fire protection unit BAK-250 Technical documentation Description CONNECTION OF VENTILATION DUCTS The fire protection unit type BAK-250 must only be connec-ted to ventilation ducts made of non-flammable materials (Construction class A to DIN 4102). The ventilation ducts used must not exert substantial forces on the fire protection unit or the suspended ceiling in case of fire. The required bellow expansion joints (flexible connection pieces) must be designed as flammable, elastic connection pieces made of at least normally inflammable building materials (EN 13501-1) and must be...
Abrir la página 3 del catálogoFire protection unit BAK-250 Technical documentation Models and dimensions MODELS AND DIMENSIONSDimensions 1 Housing 2 Shut-off damper 3 Snap-in locking device 4 Shut-off damper housing 5 Trigger device 6 Suspension lug 7 Drive (optional) 8 Fusible link cover 9 Available starting from nominal size 500 Nominal size Table 2: Available sizes Trigger device The fire protection unit is supplied as standard with an inside and an outside trigger device (fusible link with 72°C trigger temperatura)! Thus, during a fire, the trigger and closing mo-tions of the damper leaf occur independently of...
Abrir la página 4 del catálogoFire protection unit BAK-250 Technical documentation Installation details INSTALLATION DETAILS Installation The fire protection unit type BAK-250 is connected to the the ceiling with four suspensions. This is followed by mounting the suspended ceiling. Then the air diffuser is connected to the suspended ceiling or to the plenum box using a screw connection (SM mounting). The tension rod dimensions are calculated from the loads of their own weight, of the connected ducts and of the air diffuser. Installation Instructions Inserted ceiling area Fire-resistant ceiling Supply air Exhaust air...
Abrir la página 5 del catálogoFire protection unit BAK-250 Technical documentation Accessories ACCESSORIES Available at an extra charge Limit switch type ES 1 A Electric spring return actuator ELD-I-B - BFG24-T-ST SO (24 V AC/DC) - BFG230-T SO (230 V AC) Limit switch type ES 1 A Electric limit switch for position indication. Switching element including one NC and one NO contact each, 4 connections for M3.5 screw terminals for max. 2 mm². 250 V AC, Ie 6A, IP67 using suitable cable glands M20 (on-site). Figure 8: Circuit diagram limit switch type ES 1 A BAK-250 with electric spring return actuator type LD-I-B electric...
Abrir la página 6 del catálogoFire protection unit BAK-250 Technical documentation Specification texts Fire protection unit with resistance class K 90 U according to the general building supervisory approval Z-41.3-542 suitable for installation in suspended ceilings designed as panelled ceilings in screw-type and spatulated design that meet the requirements of an independent component of being fire-resistant for 90 minutes in the event of a fire from top or bottom and are classified in fire resistance class F90-A. Me-tal-cased damper leaf and visible screw connection of the air diffuser. Damper blade is triggered by an...
Abrir la página 7 del catálogoFire protection unit BAK-250 Technical documentation Maintenance or functional test MAINTENANCE OR FUNCTIONAL TEST Polluted and damp air can impair the continuous operational safety. This is why, after commissioning the ventilation installation, all shut-off devices must be subjected to a functional test at a six-month interval according to section 5 of the general building supervisory approval Z-41.3-574. If two consecutive functional tests show no defects, the shut-off devices only have to be tested at a yearly interval. If maintenance agreements are made for ventilation installations, it...
Abrir la página 8 del catálogoFire protection unit BAK-250 Technical documentation Maintenance or functional test 1.2.2 Trigger device with electric spring return actuator ELD-I-B Electric system check Actuate the electric pushbutton (on-site), this interrupts the power supply to the spring return actuator (pos.20); as a result, the shut-off damper must close automatically. Press the on-site electric pushbutton again which restores the power supply to the electric spring return actuator; as a result, the adjusting mechanism moves the shut-off damper to the OPEN position again. The pushbutton (pos.21) is pressed on the...
Abrir la página 9 del catálogoFire protection unit BAK-250 Technical documentation Maintenance or functional test SAMPLE TEMPLATES SAMPLE OF FUNCTIONAL TEST PROTOCOL SCHAKO Ferdinand Schad KG Steigstrasse 25-27 D-78600 Kolbingen Phone: +49- (0)7463 / 980-0 Fax: +49- (0)7463 / 980-200 E-mail: info@schako.de Web: www.schako.de Sample Functional test protocol for____________________ Cons. No. ____________________ Usability certificate: Series: Release device: The following function steps have been carried out according to the documents Installation, mounting and operating instructions External check: System:...
Abrir la página 10 del catálogoFire protection unit BAK-250 Technical documentation Maintenance or functional test SCHAKO Ferdinand Schad KG Steigstrasse 25-27 D-78600 Kolbingen Phone: +49- (0)7463 / 980-0 Fax: +49- (0)7463 / 980-200 E-mail: infoschako.de Web: www.schako.de Sample Functional test protocol for____________________ Cons. No. ____________________ Defects found during the test on: Defects found during the test on: Defects found during the test on: Defects found during the test on: Construction subject to change No return possible Version: 2015-08-01 | Document: 09/14 | Page 11
Abrir la página 11 del catálogoTodos los catálogos y folletos técnicos SCHAKO KG
-
CNVA
32 Páginas
-
FBS
18 Páginas
-
PIL
23 Páginas
-
MWS / MWK
23 Páginas
-
DSCXL
17 Páginas
-
DSCPL
16 Páginas
-
BKSYS
18 Páginas
-
DKA
6 Páginas
-
VMPR/VMPQ
29 Páginas
-
DSCU
18 Páginas
-
DSCP
15 Páginas
-
DQJP
9 Páginas
-
AUDIX®
25 Páginas
-
DSC
37 Páginas
-
DO
10 Páginas
-
UEKU
6 Páginas
-
UEK
6 Páginas
-
VOLKOM
6 Páginas
-
DQJ
38 Páginas
-
ALAS-F 125
6 Páginas
-
STV
8 Páginas
-
KWB
19 Páginas
-
FKU
31 Páginas
-
FKF
29 Páginas
-
DBB
27 Páginas
-
TVO
8 Páginas
-
AL
23 Páginas
-
NBS
30 Páginas
-
KGF Rejilla con filtro compacta
9 Páginas
-
JK
16 Páginas
-
HK
16 Páginas
-
FKW
28 Páginas
-
DISA-H
34 Páginas
-
DISA-360
32 Páginas
-
DISA-300
51 Páginas
-
CNV
28 Páginas
-
Aquaris-Silent
38 Páginas
-
DISA-W
41 Páginas
-
CTT
23 Páginas
-
CULTRA-Studioline
24 Páginas
-
ALPETY
16 Páginas
-
BDA
11 Páginas
-
PILB/PILBR
33 Páginas
-
DAV
19 Páginas
-
4DE
18 Páginas
-
4DF
15 Páginas
-
DQC
16 Páginas
-
DQDL
16 Páginas
-
IDA
21 Páginas
-
IKA
23 Páginas
-
ZMD
17 Páginas
-
DQF
15 Páginas
-
DQJSL
17 Páginas
-
DQJSLC
17 Páginas
-
DHV
18 Páginas
-
DSA
18 Páginas
-
DSARR
7 Páginas
-
QA
30 Páginas
-
PUSH
23 Páginas
-
WQA
12 Páginas
-
DSX
25 Páginas
-
DSX-XXL
23 Páginas
-
DSX-XXL-W
25 Páginas
-
SIA
7 Páginas
-
SAR/SAQ/SARP
13 Páginas
-
WDA
32 Páginas
-
BSG
19 Páginas
-
KG
19 Páginas
-
IB-Q
21 Páginas
-
IB-R
15 Páginas
-
PA
32 Páginas
-
DBBR
6 Páginas
-
KGRR
17 Páginas
-
DBBRR
11 Páginas
-
WGARR
7 Páginas
-
WGA
29 Páginas
-
ALA-R
4 Páginas
-
ALA-SO
4 Páginas
-
ALAS
10 Páginas
-
ALAS-P
5 Páginas
-
EBE/EBP
52 Páginas
-
DKG
6 Páginas
-
MBE/MBP
27 Páginas
-
PIANO
27 Páginas
-
VAS
26 Páginas
-
VRAPPs
20 Páginas
-
VRAQ
46 Páginas
-
VRAR
52 Páginas
-
MAK
15 Páginas
-
RS
15 Páginas
-
EasyBus
29 Páginas
-
BSK-RPR
60 Páginas
-
BKP-EN
40 Páginas
-
BAK-240
6 Páginas
-
AUDIX
2 Páginas
-
DISA
4 Páginas
-
UC-OH²
2 Páginas
-
IGA
2 Páginas
-
CDD
2 Páginas
-
MINOPAB
6 Páginas
-
ERK-SO
43 Páginas
-
MINODSA
6 Páginas
-
LAQ
11 Páginas
-
BKA-EN
79 Páginas
-
CPL
15 Páginas
-
VREX
26 Páginas
-
VQEX
17 Páginas
-
VPEX
18 Páginas
-
SVA-FS
11 Páginas
-
NRWG
22 Páginas
-
COMBIDSC
26 Páginas
-
SS-K
6 Páginas
-
GREENKIT
20 Páginas
-
SGA
5 Páginas
-
SVA-FF
15 Páginas
-
RF Return air filter grille
7 Páginas
-
MKAR_MKAQ
13 Páginas
-
KF
4 Páginas
-
Lint Separator FLARE
13 Páginas
-
FLAQ
11 Páginas
-
FG
14 Páginas
-
ERK-MB
38 Páginas
-
BKP-EN Fire damper
40 Páginas
-
BKA-UE
35 Páginas
-
BAK-250 Fire protection unit
17 Páginas
-
BAK-240
16 Páginas
-
Aquaris_KWB
20 Páginas
-
DQJF
12 Páginas
-
DQJA/DQJR
10 Páginas
-
AUDIX®-ÜSG
13 Páginas
-
DKAPPs
6 Páginas
-
DISA-Family
4 Páginas
-
RMS
11 Páginas
-
TSR
5 Páginas
-
RS-F
7 Páginas
-
VLV
31 Páginas
-
VARS
26 Páginas
-
VAQS
19 Páginas
-
MBM
10 Páginas
-
ALA
4 Páginas
-
LL
7 Páginas
-
RR-Complete
41 Páginas
-
LK
12 Páginas
-
AUDIX®-AW
20 Páginas
-
MINODSX
6 Páginas
-
MINODSA
6 Páginas
-
COMBIPIL
11 Páginas
-
COMBIDQJ
11 Páginas
-
MINOPAB
6 Páginas
-
SPB
10 Páginas
-
DISA-H
34 Páginas
-
DISA-360
32 Páginas
-
DISA-300
51 Páginas
-
AQUARIS SILENT
38 Páginas
-
NBS
24 Páginas
-
CNV
29 Páginas
-
CNVA
32 Páginas
-
JK-LP/JK-LU
15 Páginas
-
HKP / HKU
16 Páginas
-
FKW
16 Páginas
-
FLARE
13 Páginas
-
RF
7 Páginas
-
KGF
9 Páginas
-
SVA-FF
8 Páginas
-
BKA-Ü
35 Páginas
-
KF
4 Páginas