Technical Documentation "Installation, Mounting and Operating Instructions" BAK-250 Fire protection unit General building supervisory approval Z-41.3-542 SCHAKO | Ferdinand Schad KG Steigstraße 25-27 D-78600 Kolbingen

Abrir la página 1 del catálogo
BAK-250 - 2

vchAko Fire protection unit BAK-250 Technical documentation Description VENTILATION FITTINGS Exhaust air: DQJA-SR-A DQJA-SQ-A 4-DE-A DQD-L 4-DF Weight of the fire protection unit Exposed ceiling constructions can loose their strength pre-maturely. To avoid this ceiling constructions are protected with fire resistant suspended ceilings. Openings in the suspended ceiling, for example for air diffusers, are only permit-ted if they can be closed in case of fire with suitable fire protection equipment, for example with the fire protection unit type BAK-250. Fire protection unit type BAK-250 with...

Abrir la página 2 del catálogo
BAK-250 - 3

íli^ Fire protection unit BAK-250 Technical documentation Description CONNECTION OF VENTILATION DUCTS The fire protection unit type BAK-250 must only be connec-ted to ventilation ducts made of non-flammable materials (Construction class A to DIN 4102). The ventilation ducts used must not exert substantial forces on the fire protection unit or the suspended ceiling in case of fire. The required bellow expansion joints (flexible connection pieces) must be designed as flammable, elastic connection pieces made of at least normally inflammable building materials (EN 13501-1) and must be...

Abrir la página 3 del catálogo
BAK-250 - 4

Fire protection unit BAK-250 Technical documentation Models and dimensions MODELS AND DIMENSIONSDimensions 1 Housing 2 Shut-off damper 3 Snap-in locking device 4 Shut-off damper housing 5 Trigger device 6 Suspension lug 7 Drive (optional) 8 Fusible link cover 9 Available starting from nominal size 500 Nominal size Table 2: Available sizes Trigger device The fire protection unit is supplied as standard with an inside and an outside trigger device (fusible link with 72°C trigger temperatura)! Thus, during a fire, the trigger and closing mo-tions of the damper leaf occur independently of...

Abrir la página 4 del catálogo
BAK-250 - 5

Fire protection unit BAK-250 Technical documentation Installation details INSTALLATION DETAILS Installation The fire protection unit type BAK-250 is connected to the the ceiling with four suspensions. This is followed by mounting the suspended ceiling. Then the air diffuser is connected to the suspended ceiling or to the plenum box using a screw connection (SM mounting). The tension rod dimensions are calculated from the loads of their own weight, of the connected ducts and of the air diffuser. Installation Instructions Inserted ceiling area Fire-resistant ceiling Supply air Exhaust air...

Abrir la página 5 del catálogo
BAK-250 - 6

Fire protection unit BAK-250 Technical documentation Accessories ACCESSORIES Available at an extra charge   Limit switch type ES 1 A Electric spring return actuator ELD-I-B - BFG24-T-ST SO (24 V AC/DC) - BFG230-T SO (230 V AC) Limit switch type ES 1 A Electric limit switch for position indication. Switching element including one NC and one NO contact each, 4 connections for M3.5 screw terminals for max. 2 mm². 250 V AC, Ie 6A, IP67 using suitable cable glands M20 (on-site). Figure 8: Circuit diagram limit switch type ES 1 A BAK-250 with electric spring return actuator type LD-I-B electric...

Abrir la página 6 del catálogo
BAK-250 - 7

Fire protection unit BAK-250 Technical documentation Specification texts Fire protection unit with resistance class K 90 U according to the general building supervisory approval Z-41.3-542 suitable for installation in suspended ceilings designed as panelled ceilings in screw-type and spatulated design that meet the requirements of an independent component of being fire-resistant for 90 minutes in the event of a fire from top or bottom and are classified in fire resistance class F90-A. Me-tal-cased damper leaf and visible screw connection of the air diffuser. Damper blade is triggered by an...

Abrir la página 7 del catálogo
BAK-250 - 8

Fire protection unit BAK-250 Technical documentation Maintenance or functional test MAINTENANCE OR FUNCTIONAL TEST Polluted and damp air can impair the continuous operational safety. This is why, after commissioning the ventilation installation, all shut-off devices must be subjected to a functional test at a six-month interval according to section 5 of the general building supervisory approval Z-41.3-574. If two consecutive functional tests show no defects, the shut-off devices only have to be tested at a yearly interval. If maintenance agreements are made for ventilation installations, it...

Abrir la página 8 del catálogo
BAK-250 - 9

Fire protection unit BAK-250 Technical documentation Maintenance or functional test 1.2.2 Trigger device with electric spring return actuator ELD-I-B Electric system check Actuate the electric pushbutton (on-site), this interrupts the power supply to the spring return actuator (pos.20); as a result, the shut-off damper must close automatically. Press the on-site electric pushbutton again which restores the power supply to the electric spring return actuator; as a result, the adjusting mechanism moves the shut-off damper to the OPEN position again. The pushbutton (pos.21) is pressed on the...

Abrir la página 9 del catálogo
BAK-250 - 10

Fire protection unit BAK-250 Technical documentation Maintenance or functional test SAMPLE TEMPLATES SAMPLE OF FUNCTIONAL TEST PROTOCOL SCHAKO Ferdinand Schad KG Steigstrasse 25-27 D-78600 Kolbingen Phone: +49- (0)7463 / 980-0 Fax: +49- (0)7463 / 980-200 E-mail: info@schako.de Web: www.schako.de Sample Functional test protocol for____________________ Cons. No. ____________________ Usability certificate: Series: Release device: The following function steps have been carried out according to the documents Installation, mounting and operating instructions External check: System:...

Abrir la página 10 del catálogo
BAK-250 - 11

Fire protection unit BAK-250 Technical documentation Maintenance or functional test SCHAKO Ferdinand Schad KG Steigstrasse 25-27 D-78600 Kolbingen Phone: +49- (0)7463 / 980-0 Fax: +49- (0)7463 / 980-200 E-mail: infoschako.de Web: www.schako.de Sample Functional test protocol for____________________ Cons. No. ____________________ Defects found during the test on: Defects found during the test on: Defects found during the test on: Defects found during the test on: Construction subject to change No return possible Version: 2015-08-01 | Document: 09/14 | Page 11

Abrir la página 11 del catálogo

Todos los catálogos y folletos técnicos SCHAKO KG

  1. FBS

    18 Páginas

  2. PIL

    23 Páginas

  3. MWS / MWK

    23 Páginas

  4. DSCXL

    17 Páginas

  5. DSCPL

    16 Páginas

  6. BKSYS

    18 Páginas

  7. DKA

    6 Páginas

  8. VMPR/VMPQ

    29 Páginas

  9. DSCU

    18 Páginas

  10. DSCP

    15 Páginas

  11. DQJP

    9 Páginas

  12. AUDIX®

    25 Páginas

  13. DSC

    37 Páginas

  14. DO

    10 Páginas

  15. UEKU

    6 Páginas

  16. UEK

    6 Páginas

  17. VOLKOM

    6 Páginas

  18. DQJ

    38 Páginas

  19. ALAS-F 125

    6 Páginas

  20. STV

    8 Páginas

  21. KWB

    19 Páginas

  22. FKU

    31 Páginas

  23. FKF

    29 Páginas

  24. DBB

    27 Páginas

  25. TVO

    8 Páginas

  26. AL

    23 Páginas

  27. NBS

    30 Páginas

  28. KGF

    9 Páginas

  29. JK

    16 Páginas

  30. HK

    16 Páginas

  31. FKW

    28 Páginas

  32. DISA-H

    34 Páginas

  33. DISA-B

    32 Páginas

  34. DISA-601

    41 Páginas

  35. DISA-360

    32 Páginas

  36. DISA-300

    51 Páginas

  37. CNVA

    32 Páginas

  38. CNV

    28 Páginas

  39. Aquaris-Silent

    38 Páginas

  40. DISA-W

    41 Páginas

  41. CTT

    23 Páginas

  42. CULTRA-Studioline

    24 Páginas

  43. ALPETY

    16 Páginas

  44. BDA

    11 Páginas

  45. PILB/PILBR

    33 Páginas

  46. DAV

    19 Páginas

  47. 4DE

    18 Páginas

  48. 4DF

    15 Páginas

  49. DQC

    16 Páginas

  50. DQDL

    16 Páginas

  51. IDA

    21 Páginas

  52. IKA

    23 Páginas

  53. ZMD

    17 Páginas

  54. DQF

    15 Páginas

  55. DQJSL

    17 Páginas

  56. DQJSLC

    17 Páginas

  57. DHV

    18 Páginas

  58. DSA

    18 Páginas

  59. DSARR

    7 Páginas

  60. QA

    30 Páginas

  61. PUSH

    23 Páginas

  62. WQA

    12 Páginas

  63. DSX

    25 Páginas

  64. DSX-XXL

    23 Páginas

  65. DSX-XXL-W

    25 Páginas

  66. SIA

    7 Páginas

  67. SAR/SAQ/SARP

    13 Páginas

  68. WDA

    32 Páginas

  69. BSG

    19 Páginas

  70. KG

    19 Páginas

  71. IB-Q

    21 Páginas

  72. IB-R

    15 Páginas

  73. PA

    32 Páginas

  74. DBBR

    6 Páginas

  75. KGRR

    17 Páginas

  76. DBBRR

    11 Páginas

  77. WGARR

    7 Páginas

  78. WGA

    29 Páginas

  79. ALA-R

    4 Páginas

  80. ALA-SO

    4 Páginas

  81. ALAS

    10 Páginas

  82. ALAS-P

    5 Páginas

  83. EBE/EBP

    52 Páginas

  84. DKG

    6 Páginas

  85. MBE/MBP

    27 Páginas

  86. PIANO

    27 Páginas

  87. VAS

    26 Páginas

  88. VRAPPs

    20 Páginas

  89. VRAQ

    46 Páginas

  90. VRAR

    52 Páginas

  91. MAK

    15 Páginas

  92. RS

    15 Páginas

  93. EasyBus

    29 Páginas

  94. BSK-RPR

    60 Páginas

  95. BKP-EN

    40 Páginas

  96. BAK-240

    6 Páginas

  97. AUDIX

    2 Páginas

  98. DISA

    4 Páginas

  99. UC-OH²

    2 Páginas

  100. IGA

    2 Páginas

  101. CDD

    2 Páginas

  102. MINOPAB

    6 Páginas

  103. ERK-SO

    43 Páginas

  104. MINODSA

    6 Páginas

  105. LAQ

    11 Páginas

  106. BKA-EN

    79 Páginas

  107. CPL

    15 Páginas

  108. VREX

    26 Páginas

  109. VQEX

    17 Páginas

  110. VPEX

    18 Páginas

  111. SVA-FS

    11 Páginas

  112. NRWG

    22 Páginas

  113. COMBIDSC

    26 Páginas

  114. SS-K

    6 Páginas

  115. GREENKIT

    20 Páginas

  116. SGA

    5 Páginas

  117. SVA-FF

    15 Páginas

  118. RF

    7 Páginas

  119. MKAR_MKAQ

    13 Páginas

  120. KF

    4 Páginas

  121. FLARE

    13 Páginas

  122. FLAQ

    11 Páginas

  123. FG

    14 Páginas

  124. ERK-MB

    38 Páginas

  125. BSK-RPR

    60 Páginas

  126. BKP-EN

    40 Páginas

  127. BKA-UE

    35 Páginas

  128. BAK-250

    17 Páginas

  129. BAK-240

    16 Páginas

  130. Aquaris_KWB

    20 Páginas

  131. DQJF

    12 Páginas

  132. DQJA/DQJR

    10 Páginas

  133. AUDIX®-ÜSG

    13 Páginas

  134. DKAPPs

    6 Páginas

  135. DISA-Family

    4 Páginas

  136. RMS

    11 Páginas

  137. TSR

    5 Páginas

  138. RS-F

    7 Páginas

  139. VLV

    31 Páginas

  140. VARS

    26 Páginas

  141. VAQS

    19 Páginas

  142. MBM

    10 Páginas

  143. ALA

    4 Páginas

  144. LL

    7 Páginas

  145. RR-Complete

    41 Páginas

  146. LK

    12 Páginas

  147. AUDIX®-AW

    20 Páginas

  148. MINODSX

    6 Páginas

  149. MINODSA

    6 Páginas

  150. COMBIPIL

    11 Páginas

  151. COMBIDQJ

    11 Páginas

  152. MINOPAB

    6 Páginas

  153. SPB

    10 Páginas

  154. DISA-H

    34 Páginas

  155. DISA-601

    41 Páginas

  156. DISA-360

    32 Páginas

  157. DISA-300

    51 Páginas

  158. DISA-B

    32 Páginas

  159. AQUARIS SILENT

    38 Páginas

  160. NBS

    24 Páginas

  161. CNV

    29 Páginas

  162. CNVA

    32 Páginas

  163. JK-LP/JK-LU

    15 Páginas

  164. HKP / HKU

    16 Páginas

  165. FKW

    16 Páginas

  166. FLARE

    13 Páginas

  167. RF

    7 Páginas

  168. KGF

    9 Páginas

  169. SVA-FF

    8 Páginas

  170. BKA-Ü

    35 Páginas

  171. KF

    4 Páginas